TPI Europe is committed to safety.
skip to Main Content
login to customer portal                request service                     contact us                  visit TPI worldwide  
717R Flue Gas Analyser Kit 4
717R Flue Gas Analyser Kit 4
719 Gas Sniffer
CK21M Pipe Clamp Probes Pair
A740 Infrared Printer
717R Flue Gas Analyser
717R Flue Gas Analyser

717R Kit 4

£590.00

The TPI 717R Flue Gas Combustion Analyser is a state of the art, easy to use analyser designed not only to display and calculate the required readings from a flue but also to cover most of the other desirable parameters associated with appliance installation and maintenance.

Kit 4 contains all Standard Accessories and includes:
A740 Infrared Printer
2 X CK21M Pipe Clamp Probes
719 Gas Sniffer

In stock

Description

717R Kit 4 with Standard Accessories and includes:
A740 Infrared Printer
2 X CK21M Pipe Clamps
719 Gas Sniffer

  • TPI 717R Analyser
  • Rubber Boot (A765)
  • Soft Carrying Case (A768)
  • Sampling Probe (c/w Type “K” Thermocouple)
  • In-Line Water Trap Bowl Filter (c/w Spare Particle Filter)
  • Battery Charger (A766)
  • Mini In-Line Pump Protection Filter (c/w 5 spare filters)
  • Exhaust Spigot Removable (A764)
  • Battery Charger (A766) – 1 each
  • Mini Pump Protection Filter Assembly (A763) – 1 each
  • Exhaust Spigot Removable (A764) – 1 each
  • Pressure Tubing (2 x 1 metres)

For full product details and Kit Options please visit the product page here 717R Flue Gas Analyser

Additional information

Weight3 kg
Dimensions46 × 30 × 19 cm

Video

Details

  • Combustion Efficiency Analyser: Measure O2, CO, and flue temperature. Calculate efficiency, excess air, CO2 & (CO/CO2) Ratio.
  • CO Analyser: Measure carbon monoxide in ambient air.
  • Differential Manometer: +/- 150 mBar (0.01 mBar resolution). Great for tightness/let by or burner pressure testing.
  • Differential Thermometer: Dual input K-Type thermocouple thermometer measures differential temperatures. Ideal for measuring & recording flow & return temperatures.
  • Six Year Warranty

All of the features of the 709R plus:

  • Timed Let/By & Tightness Test
  • Timed CO Build-Up Room Test
  • Integrated Magnet
  • Calibration Due Countdown on switch on
  • Serial Number on Print-Outs
  • Next Calibration Due Date on Print-Outs

Standards

The TPI 717R conforms to EN50379 and is suitable for engineers working with BS7967, the usage standard.

Serial Number & Next Cal Due Date are printed at the bottom of each print-out ensuring that you always know your readings have been taken with the correct in-calibration flue gas analyser giving you complete peace of mind.

HHIC: The Heating & Hotwater Industry Council made a recommendation that from April 2013 that the CO level & CO/CO2 (Ratio) reading in a flue is recorded when a boiler is commissioned and that this practise become mandatory from April 2014. Please click here for further details.

The recording of the CO level and Ratio reading will become a mandatory part of completing the Benchmark Form.

Combustion Performance Analysis (CPA1): From April 2012 it has been compulsory for all engineers to acquire CPA1 Assessment to prove their competency in using a Flue Gas Analyser. Please click here for complete details.

Documentation

717R Data Sheet

717R Instruction Manual

Specifications

Model 717R Specifications
 Instrument
 Operating Temperature Range14°F to +122°F (-10°C to +50°C)
 Battery / Batery LifeRechargeable Ni-MH / > 6 Hours
 Charger Input Voltage115V or 230V : 50/60 Hz AC
 FuelsNatural Gas, LPG, Light Oil, Heavy Oil, Bituminous Coal, Anthracite Coal, Coke, Butane, Wood, Bagasse
 Pressure Rangesmbar, kPa & inH2O
 DisplayBacklit Graphic LCD
 Data Storage50 sets of readings, multiple pages
 Time and Date24 Hour Real Time Clock
 Dimensions200mm x 90mm x 60mm
 Weight500g
 CasingRubber Boot as Standard
 Switch OffFailsafe
 ExhaustSafety Spigot
 Conforms toEN50379

 

 Flue Temperature Probe
 Construction Pistol Grip with Stainless Steel Shaft
 Hose Length 2500mm
 Insertion Length 200mm
 ‘K’ Type Thermocouple Accuracy +/- 0.3%, +/- 1˚C
 Maximum Temperature 800°C

 

 Gases Range Resolution Accuracy
 Oxygen 0-25% 0.1% +/- 0.3%
 Carbon Monoxide 0-10,000 ppm 1 ppm <20ppm +/- 3 ppm
>100ppm +/- 5%
 Carbon Dioxide (calculated) 0-25% 0.1% +/- 0.3%
 Combustion Efficiency 0-100% 0.1%

 

 Pressure Measurement
 Selectable Ranges mbar, kPa and inH2O
 Range – 150 mbar to + 150 mbar
 Resolution 0.01 mbar & 0.1 mbar
 Accuracy +/- 0.5% fsd

You may also like…